Installation Tips

18th January
2010
written by boilerman
Please refer to the Nimbus Manual for specific guidance on configuring your variable speed controller.
Fixed Speed 50

The purpose of using the nimbus control is so the ideal flow rate can be achievable for any circulator in your system. Flow rate is important. A boiler circulator running too slowly can overheat, whereas running too quickly can negatively affect stratification in thermal storage tanks by stirring the hot and cold water.

Using the manual dip switch settings on the nimbus, you can test different speeds in order to determine the best flow rate for transferring heat.

The default settings are with all switches in the off position as seen here.

Default Nimbus Settings

Using the dip switches, you can manually set the controller to a fixed speed. You are able to configure it in one percent increments between 27 and 100 percent output. Please note, we have found most circulators to be unable to work below 40 percent as set on the nimbus control.

Fixed Speed 27
Fixed Speed 50

Using the Nimbus controller in this manner will give you a single user defined speed for most any circulator. Our personal experience is with using the TACO circulators, 007, 0010, 0014 models.

Using Nimbus for True Variable Speed with NFCS

Another way to use the nimbus is in conjunction with a nofossil control system, NFCS, which I have installed at my own home, which can be seen live, here.   The analog out(AO), on the left hand column are the four outputs being controlled with 4-20ma control signal.

The benefit of using the Nimbus with the NFCS is to drive your circulator speeds dynamically based on current heating system temperatures and rule sets. This allows you to have even greater control over your heating system and also run your system at its optimum settings.

In this setup, the output of the Nimbus control is being controlled by the NFCS via a 4-20ma signal. The NFCS connects directly to each specific nimbus controller with a signal wire coming through a variable speed breakout box.

One of the first things you need to do when setting up your variable speed controller to work with NFCS is to configure the jumper so it will work with 4-20ma signal.

Using the manual we can determine how to best set the Nimbus for our system.   This is an example of a configuration, set to run on current control. This example is also to run at 60 percent if no signal is present. Where the manual refers to a “fan”, this applies to the circulator in our scenario.

A. Fan On / Fan Off Feature (switch #1): To turn fan(s) off below the set idle speed (see table 3). Set switch #1 to the ON position. To keep fans running at idle speed below the set idle speed, set switch #1 to the OFF position.

B. Idle Speed DIP Switch Settings

C. Control Signal Loss Options (switch#6): If the control signal is lost, (less than 4mA in I mode, less than 2VDC in V mode) when switch 6 is OFF fans will continue to idle or remain off. To send fans to full speed if the control signal is lost, set switch 6 to the ON position.

D.
Setting Control Modes

In the event that the NFCS is offline and not supplying 4-20ma signals, the nimbus can be configured so that it can either run in one of four preselected idle speeds or simply run wide open assuming that the aquastat or other control switch is supplying line voltage to the nimbus.

Connecting a variable speed control unit to the NFCS

Please refer to the Nimbus Manual for specific guidance on configuring your variable speed controller.
3rd November
2008
written by Mike Matlosz

Is a hot water storage tank required?
It is highly recommended because it increases overall system efficiency, is more convenient and minimizes the possibility of creosote build up.

storage tank

Hot water storage tank before it was insulated

Efficiency:
A properly sized hot water storage tank can lessen your wood usage. The average American house uses about 82 Million Btu’s annually. Assuming the boiler system is 85% efficient, 82 Million Btu’s translates into 4 – 5.25 hardwood cords or 6.5 to 11.75 softwood cords.

The increased efficiency is due to the fact that the boiler is designed to operate best when burning at full pace. The hot water tank stores heat for later, and allows the boiler to continue to burn for a longer period of time at maximum output. Once the demand is finally met, the boiler will idle.

Convenience:
Because the heat is stored in the tank, the heat is retained long after the wood or coal is depleted (the length of time is variable based on demand and on the volume of water in the tank). This means that you don’t have to reload your boiler until your tank temperature drops to an unusable temperature (the unusable temperature varies based on your heating system. Typical unusable temperatures are below 140 degrees for baseboard and below 110 for radiant floor).

Starting the fire once every few days is sufficient during warmer months in fall and spring or in the summer when using the boiler only for domestic hot water. So ultimately, even though the boiler will produce heat without the additional storage tank, the added efficiency and convenience exceeds the initial investment of a tank.

Creosote:
When you size your boiler, typically you are trying to size it for the coldest temperature your area sees in the winter. Our area is 0 degrees. We may see 0 degrees for a week or two out of the year, so that means that 90% of the time our boiler is “over sized”. This means that in the spring and autumn months the boiler will tend to idle more if no storage tank is used.

When the boiler is idling, you have the potential to build up creosote in your primary chamber and chimney. If a hot water storage tank is in use, it allows the boiler to burn at full capacity for a longer period of time when first lit. This allows the tar and creosote causing agents to be burned off during the gasification. If system demand is met near the end of the burn, the fuel left is in a charcoal state.  If the boiler idles at this point, it will not cause any creosote.